Back to dashboard
Sections menu

Airbus A320ceo / neo · ATA systems manual

ATA chapters

Each system organised by its ATA 100 chapter number, the way maintenance and operations manuals are structured: components, how it operates, controls, indications, failures and maintenance.

Unverified — check your manualText on this page is written from general knowledge. Figures marked ✓ are checked against official FAA/EASA data.See verified data

ATA 21

Air Conditioning & Pressurisation

Two air-cycle packs condition engine or APU bleed air. A mixer unit blends pack and recirculated cabin air. Two cabin pressure controllers (CPC) automatically schedule the outflow valve.

Where it is

Location of Air Conditioning & Pressurisation
Air Conditioning & Pressurisation

What it looks like

Pack bay under the belly with heat exchangers and ducts
Pack bay under the belly with heat exchangers and ducts · illustrative image
Components in ATA 21 →

Technical data

ItemValue
Max differentialapprox. 8.6 psi (relief approx. 8.6/9 psi)
Max cabin altitude (normal)approx. 8,000 ft
ZonesCockpit, FWD cabin, AFT cabin

Components

1.Packs (2)

Air-cycle machine: primary heat exchanger, compressor, main heat exchanger, turbine, water separator.

Each A320 has two air-cycle packs mounted in the belly fairing below the wing centre section, fed by bleed air from the engines, APU or ground cart via the pneumatic system. They are the primary source of conditioned and pressurized air for the cabin and cockpit.

How it works
  • Hot bleed air is cooled in the primary heat exchanger by ram air, compressed by the ACM compressor, cooled again in the main heat exchanger, then expanded across the ACM turbine, dropping temperature sharply.
  • The turbine drives the compressor on a common shaft, and a water separator downstream removes condensed moisture before mixing with recirculated air.
  • Pack outlet temperature is modulated by a pack flow control valve and a bypass valve commanded by the zone controller to reach the demanded duct temperature.
  • Each pack can run in LO, NORM or HI flow depending on bleed pressure, electrical load and cooling demand from the cabin and avionics.
Bleed supply pressureapprox. 30-45 psi
Pack outlet temperature rangeapprox. 5 to 90 deg C
Max continuous flowHI flow approx. 100 percent
Failures
  • Pack fault / overheat: ECAM PACK 1(2) FAULT, pack automatically shuts off, remaining pack and ram air supply cabin
  • ACM turbine bearing failure: Loss of cooling, possible smoke smell in bleed air, pack isolated
Inspection
  • Inspect pack bay drains and check valves for blockage
  • Borescope/visual check of heat exchanger matrices for fouling
  • Verify pack valve rigging and leak check of ducts

2.Pack flow control valves

Regulate flow (LO/NORM/HI).

Electrically controlled, pneumatically operated valves located at the pack inlet ducting in the belly fairing, one per pack, that set the quantity of bleed air admitted to each air-cycle machine.

How it works
  • The valve is commanded by the Air Conditioning System Controller (zone controller) to one of LO, NORM or HI flow positions depending on cabin demand and bleed availability.
  • Flow rate directly affects pack discharge temperature and cooling capacity, so the controller trims it along with the trim air valves to hold selected zone temperatures.
  • Position feedback is sent back to the controller and displayed on the ECAM BLEED/COND page.
  • On loss of a pack or bleed source, the opposite pack's flow valve may be driven to HI to compensate.
Flow positionsLO / NORM / HI
ActuationPneumatic motor, electrically commanded
Failures
  • Valve stuck closed: Loss of pack flow, ECAM PACK FAULT, reduced cabin cooling/pressurization margin
  • Valve stuck open: Excess bleed draw, possible duct over-temperature protection trip
Inspection
  • Functional check of valve travel and position indication
  • Inspect actuator linkage and electrical connector for corrosion

3.Mixer unit

Mixes pack air with recirculated air.

A ducting assembly located above the cabin ceiling near the wing box where conditioned air from both packs is combined with cabin recirculated air before distribution to the cockpit and cabin zones.

How it works
  • Pack discharge air at low temperature mixes with warm recirculated cabin air drawn by two recirculation fans, raising the mix temperature and reducing total fresh-air bleed demand.
  • The mixed air is then split and passed through trim air valves for each zone to achieve the individually selected temperatures.
  • A HEPA-equivalent recirculation filter upstream removes particulates and some bacteria from the recirculated portion.
  • Mix ratio is largely fixed by duct geometry; temperature control is achieved downstream by trim air, not by varying the mix itself.
Recirculation fans2, electrically driven
Typical recirc fractionapprox. 40-50 percent of total supply air
Failures
  • Recirculation fan failure: ECAM caution, reduced total airflow, slightly lower cabin temperature uniformity
  • Mixer duct leak: Loss of conditioned air to distribution, possible uneven zone temperatures
Inspection
  • Inspect mixer casing and duct joints for leaks
  • Check recirculation filter condition per maintenance schedule

4.Trim air valves

Add hot air per zone for temperature control.

Small pneumatic valves, one per cabin/cockpit zone, located in the mixer manifold area, that add a controlled trickle of hot (unmixed pack bypass) bleed air to the cold mixed air feeding each zone duct.

How it works
  • Each zone has its own temperature selector (cockpit, forward cabin, aft cabin); the zone controller compares selected to sensed duct/zone temperature and modulates the trim air valve accordingly.
  • Opening the valve raises that zone's supply temperature without affecting the other zones, allowing independent temperature control from a common cold air supply.
  • Hot trim air is tapped from upstream of the pack's cooling turbine so it is still regulated bleed pressure air.
  • A duct overheat sensor can command the trim valve closed if duct temperature exceeds limits.
Number of zones3 (cockpit, fwd cabin, aft cabin) typical
Trim air sourcepre-cooled bleed air upstream of pack turbine
Failures
  • Trim valve stuck open: Zone overheats, ECAM duct overheat caution possible
  • Trim valve stuck closed: Zone cannot be warmed, persistent cold complaint in that zone
Inspection
  • Functional test of zone temperature selection response
  • Inspect valve actuator and duct overheat sensor wiring

5.Outflow valve

Rear fuselage; motor-driven by the active CPC.

A single large butterfly-type valve in the lower rear fuselage that is the primary means of controlling cabin pressure by metering the rate at which cabin air is discharged overboard.

How it works
  • It is driven by two motors, normally controlled automatically by the active Cabin Pressure Controller (CPC) which schedules cabin altitude as a function of flight phase and landing field elevation entered in the MCDU.
  • The motor positions the valve to balance incoming pack flow against outflow, maintaining a target cabin pressure differential of up to approximately 8.6 psi.
  • A second CPC and a manual mode allow crew backup control of the valve via a rotary switch on the overhead panel if automatic control fails.
  • The valve fully opens on the ground via landing gear squat switch logic to equalize cabin pressure before door opening.
Max differential pressureapprox. 8.6 psi
Controldual CPC, manual backup via overhead switch
Failures
  • Valve motor failure: ECAM CAB PR FAULT, switch to backup CPC/manual mode
  • Valve stuck open: Cabin unable to pressurize, emergency descent may be required
Inspection
  • Visual inspection of valve blade and seals for corrosion/wear
  • Functional test of automatic and manual operation during pressurization checks

6.Safety valves (2)

Overpressure and negative-pressure relief.

Two spring-loaded pressure relief valves in the aft fuselage pressure bulkhead area, independent of the outflow valve, that protect the fuselage from both over- and under-pressurization.

How it works
  • Each safety valve opens automatically if cabin differential pressure exceeds the structural limit, venting excess pressure overboard regardless of outflow valve or CPC status.
  • A negative pressure relief function (sometimes a separate flapper) opens if outside pressure exceeds cabin pressure, preventing structural damage from negative differential.
  • They are purely mechanical/pneumatic, requiring no electrical power, providing a last-line passive safeguard.
  • Their setpoints are fixed and not adjustable from the cockpit.
Positive relief setpointapprox. 8.9-9.0 psi differential
Negative relief setpointapprox. -1 psi differential
Failures
  • Valve seized shut: Loss of overpressure protection, airworthiness item if found during check
  • Valve leaking: Minor unexplained cabin pressure loss, ECAM CAB PR indications
Inspection
  • Functional pressure test during scheduled maintenance
  • Inspect valve seat and seal for corrosion or debris

Operation

  • The zone controller computes required temperature; packs deliver air for the coldest zone and trim air heats the others.
  • CPCs use landing elevation from the FMGS and alternate automatically each flight. MAN mode drives the outflow valve directly.

Controls

ControlFunction
PACK 1/2On/off.
PACK FLOWLO/NORM/HI.
Zone temperature selectorsCockpit/FWD/AFT.
MODE SEL / MAN V/S CTL / LDG ELEVPressurisation panel.
DITCHINGCloses outflow valve and inlets.

Indications

IndicationMeaning
SD CAB PRESS pageΔp, cabin V/S, cabin altitude, outflow valve position.
SD COND pageZone and duct temps.
CAB PR EXCESS CAB ALTCabin altitude > 9,550 ft: emergency descent.

Failures & crew actions

FailureEffect / action
PACK 1(2) FAULTPack valve disagree or pack outlet overheat; pack off, descend if needed for single pack.
CAB PR SYS 1+2 FAULTUse MAN pressurisation.
Excess cabin altitudeMasks on, emergency descent.

Maintenance

  • Pack heat exchanger cleaning per MPD.
  • Outflow valve operational test.
  • Recirculation filter replacement.

Deep dive · ATA 21

Air Conditioning & Pressurisation — in depth

Packs

Two air conditioning packs in the belly fairing take hot bleed air (about 200 °C) via the pack flow control valves. Each pack is an air-cycle machine: primary heat exchanger, compressor, main heat exchanger, turbine (expansion cools the air well below 0 °C) and water extractor.

Pack outlet air goes to the mixer unit where it mixes with recirculated cabin air (filtered). Hot trim air is added per zone (cockpit, fwd cabin, aft cabin) to reach the selected temperature, controlled by the zone controller and two pack controllers.

Packs2 air-cycle machines
ZonesCockpit, FWD cabin, AFT cabin
Temperature selection18–30 °C
Pack flow selectorLO / NORM / HI
RecirculationApprox. 40–50 % of cabin airflow through HEPA filters

Pressurisation control

Two Cabin Pressure Controllers (CPC) operate automatically, one active and one standby, swapping each flight. They modulate the single outflow valve in the aft fuselage, using the FMGS landing elevation and QNH data to schedule cabin altitude.

Two safety valves open at about 8.6 psi positive differential, and also prevent negative differential greater than about −1 psi.

Max differential8.6 psi (safety valve)
Normal max cabin altitudeapprox. 8 000 ft
Cabin altitude warning9 550 ft (+/−350)
DitchingCloses outflow valve, inlet and extract valves

Pressurisation failures

CAB PR SYS 1 FAULTAutomatic transfer to system 2 — no action
CAB PR SYS 1+2 FAULTMODE SEL to MAN; control V/S with MAN V/S CTL toggle
CAB PR EXCESS CAB ALTMasks on, descent per ECAM (emergency descent if required)
LDG ELEV FAULTSet landing elevation manually

Warning · Excessive cabin altitude: crew oxygen masks on and establish communication first — time of useful consciousness at FL350 is only about 30–60 seconds.

Educational summary — verify against the official AMM/FCOM/POH for your aircraft.

EDUCATIONAL USE ONLY. Content is summarised from manufacturer documentation for learning. It is not approved flight or maintenance data. Always use the current, aircraft-specific POH/AFM, FCOM, QRH, AMM and operator procedures.